Data from Sustainability Base Characterizing Hot Water Pump Differential Pressure Spikes for ACCEPT

During the heating season in Sustainability Base, a critical alarm associated with a hot water pump circulating heating water for the radiative system which exchanges heat via a geothermal heat pump was found. After further investigation it was ascertained that many such alarms were experienced throughout the entire heating season. These alarms are triggered as a result of the excursion of the hot water differential pressure outside of a nominal operating envelope for a fixed duration. There is a control system associated with regulating the hot water pump differential pressure to a fixed operating setpoint, and there are natural variations in the system that allow the pressure to be regulated and maintained within these nominal operating bounds. However, when system changes occur such as valves opening or closing to support the distribution of hot water through PVC piping to areas of the building where heating demand is called for in response to zone temperature requirements, the pump's operating speed must change accordingly to maintain this setpoint. If the pump speed does not change quickly enough to accommodate heating demand, these alarms can result and consequentially water hammer can occur, which may lead to accelerated aging of the PVC piping infrastructure as well as fittings, elbows, etc. In the worst case scenario it could cause leaking or bursting pipes.

The zip file linked contains three subdirectories and a parameter list to be used for processing using ACCEPT. Datafiles are partitioned into training, validation, and testing sub-directory structures. A text file contains all parameter identifiers associated with the cold complaint prediction scenario. Please note that the parameter list is a text file containing the following lines:

DCHWSSF - South Wing water flow rate DCHWSNF - North Wing water flow rate DCHWDP - Hot Water Pump Differential Pressure DCHWP1SP - Hot Water Pump Differential Speed DCHWP1S - Hot Water Pump Status Indicator

The last parameter in this list is intended only to provide indication of ground truth (pump exceedances), and is not meant to construct models in ACCEPT. Data was collected from November 03, 2014 to February 03, 2015, and the alarm threshold limits of operation are flagged above 6.0 psid and below 4.5 psid. It should be noted the normal operation for the pump includes periods when it is off, when it retains a residual static pressure (~ 1.0 psid). The static binary indicator provides this information.

Data and Resources

Additional Info

Field Value
Maintainer RODNEY MARTIN
Last Updated March 31, 2025, 18:57 (UTC)
Created March 31, 2025, 18:57 (UTC)
accessLevel public
accrualPeriodicity irregular
bureauCode {026:00}
catalog_@context https://project-open-data.cio.gov/v1.1/schema/catalog.jsonld
catalog_@id https://data.nasa.gov/data.json
catalog_conformsTo https://project-open-data.cio.gov/v1.1/schema
catalog_describedBy https://project-open-data.cio.gov/v1.1/schema/catalog.json
harvest_object_id 4c159ebd-8e4a-4ed8-bca3-2c087b2eeceb
harvest_source_id 61638e72-b36c-4866-9d28-551a3062f158
harvest_source_title DNG Legacy Data
identifier DASHLINK_946
issued 2016-01-15
landingPage https://c3.nasa.gov/dashlink/resources/946/
modified 2020-01-29
programCode {026:029}
publisher Dashlink
resource-type Dataset
source_datajson_identifier true
source_hash 586f38dbc251d35bd1767f3e5ba8427b19327204ce8b12343fe6d8cd18d2ffb2
source_schema_version 1.1